XM3.1-905-HPL
Power Supply Events
 
 

Alarms
 

Battery
 

Displayed time zone:
<<Prev 1 2 3 4 5 6 7 8 Next>>
Power Supply Events
  Time Event Description
261 2021-11-05 16:08:19 2001 15:55:14 11/05/21785s UTILITY EVENT: OUTAGE
260 2021-11-05 15:14:24 2001 15:02:58 11/05/21686s UTILITY EVENT: OUTAGE
259 2021-11-05 14:34:18 2038 WARNING :XM3-1 ACTIVE DROP =1 NEW: 186W, OLD: 260W
258 2021-11-05 14:28:52 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
257 2021-11-05 14:28:45 2001 14:16:28 11/05/21737s UTILITY EVENT: OUTAGE
256 2021-11-05 14:16:27 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
255 2021-11-05 14:07:33 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
254 2021-11-05 13:59:05 202B ALARM CLEARED :XM3-1 LOW BATTERY WARNING=OK
253 2021-11-05 13:58:05 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
252 2021-11-05 13:57:57 2029 MAJOR ALARM :XM3-1 LOW BATTERY WARNING=ALARM
251 2021-11-05 13:51:51 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
250 2021-11-05 13:51:43 2001 13:39:26 11/05/21737s UTILITY EVENT: OUTAGE
249 2021-11-05 13:39:24 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
248 2021-11-05 13:36:35 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
247 2021-11-05 13:07:19 202B ALARM CLEARED :XM3-1 LOW BATTERY WARNING=OK
246 2021-11-05 13:06:35 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
245 2021-11-05 13:06:21 2029 MAJOR ALARM :XM3-1 LOW BATTERY WARNING=ALARM
244 2021-11-05 13:05:52 202B ALARM CLEARED :XM3-1 OUTPUT OVERLOAD =OK
243 2021-11-05 13:05:43 2029 MAJOR ALARM :XM3-1 OUTPUT OVERLOAD =ALARM
242 2021-11-05 13:04:58 202E CLOCK DEFAULTED 13:04:58 11/05/21
241 2021-11-05 13:04:58 202B ALARM CLEARED :XM3-1 APP CLOCK NOT SET=0
240 2021-11-05 13:03:50 201A ALARM CLEARED :XM3-1 OUTPUT FAIL ALARM=OK
239 2021-11-05 12:59:08 201A MAJOR ALARM :XM3-1 OUTPUT FAIL ALARM=ALARM
238 2021-11-05 12:59:46 2038 WARNING :XM3-1 ACTIVE DROP =1 NEW: 0W, OLD: 103W
237 2021-11-04 22:50:49 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
236 2021-11-04 22:50:42 2001 22:33:10 11/04/21 17m UTILITY EVENT: OUTAGE
235 2021-11-04 22:33:09 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
234 2021-11-04 22:29:29 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
233 2021-11-04 22:14:01 202B ALARM CLEARED :XM3-1 LOW BATTERY WARNING=OK
232 2021-11-04 22:12:29 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
231 2021-11-04 22:12:20 2029 MAJOR ALARM :XM3-1 LOW BATTERY WARNING=ALARM
230 2021-11-04 22:08:29 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
229 2021-11-04 22:08:23 2001 21:54:51 11/04/21812s UTILITY EVENT: OUTAGE
228 2021-11-04 21:54:50 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
227 2021-11-04 21:50:44 202E CLOCK DEFAULTED 21:50:44 11/04/21
226 2021-11-04 21:50:44 202B ALARM CLEARED :XM3-1 APP CLOCK NOT SET=0
225 2021-11-04 21:45:08 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
224 2021-11-04 21:44:54 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
223 2021-11-04 21:12:24 2001 21:00:22 11/04/21722s UTILITY EVENT: OUTAGE
222 2021-11-04 20:24:27 2001 20:11:16 11/04/21791s UTILITY EVENT: OUTAGE
221 2021-11-04 19:11:56 2001 18:59:36 11/04/21740s UTILITY EVENT: OUTAGE
220 2021-11-04 18:32:21 2001 18:20:22 11/04/21719s UTILITY EVENT: OUTAGE
219 2021-11-04 17:49:13 2001 17:34:50 11/04/21863s UTILITY EVENT: OUTAGE
218 2021-11-04 17:05:24 2001 16:51:37 11/04/21827s UTILITY EVENT: OUTAGE
217 2021-11-04 16:21:30 202B ALARM CLEARED :XM3-1 LOW BATTERY WARNING=OK
216 2021-11-04 16:20:21 2029 MAJOR ALARM :XM3-1 LOW BATTERY WARNING=ALARM
215 2021-11-04 16:01:18 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
214 2021-11-04 16:00:26 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
213 2021-11-04 16:00:24 202B ALARM CLEARED :XM3-1 LOW BATTERY WARNING=OK
212 2021-11-04 16:00:18 2029 MAJOR ALARM :XM3-1 LOW BATTERY WARNING=ALARM
211 2021-11-04 15:11:21 2038 WARNING :XM3-1 ACTIVE DROP =1 NEW: 303W, OLD: 359W
210 2021-11-04 15:08:22 202B ALARM CLEARED :XM3-1 OUTPUT OVERLOAD =OK
209 2021-11-04 14:42:32 2029 MAJOR ALARM :XM3-1 OUTPUT OVERLOAD =ALARM
208 2021-11-04 14:18:46 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
207 2021-11-04 14:18:39 2001 14:05:13 11/04/21806s UTILITY EVENT: OUTAGE
206 2021-11-04 14:05:12 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
205 2021-11-04 12:49:55 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
204 2021-11-04 12:49:49 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
203 2021-11-04 12:31:18 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
202 2021-11-04 12:20:30 202E CLOCK DEFAULTED 12:20:30 11/04/21
201 2021-11-04 12:20:30 202B ALARM CLEARED :XM3-1 APP CLOCK NOT SET=0
200 2021-11-04 12:14:39 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
199 2021-11-04 12:15:51 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
198 2021-11-04 12:14:50 202A MINOR ALARM :XM3-1 BATT TEMP PROBE =ALARM
197 2021-10-29 19:54:17 202E CLOCK DEFAULTED 19:54:17 10/29/21
196 2021-10-29 19:54:17 202B ALARM CLEARED :XM3-1 APP CLOCK NOT SET=0
195 2021-10-29 19:48:44 202B ALARM CLEARED :XM3-1 BATT TEMP PROBE =OK
194 2021-10-29 19:48:26 202A MINOR ALARM :XM3-1 BATT TEMP PROBE =ALARM
193 2021-10-29 19:48:13 202A MINOR ALARM :XM3-1 BATT TEMP PROBE =ALARM
192 2021-10-29 19:48:13 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
191 2021-10-29 19:47:51 2001 19:47:22 10/29/21 29s UTILITY EVENT: OUTAGE
190 2021-10-29 19:46:49 2001 19:46:29 10/29/21 20s UTILITY EVENT: OUTAGE
189 2021-10-29 19:46:01 2001 19:45:50 10/29/21 11s UTILITY EVENT: OUTAGE
188 2021-10-29 19:45:07 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
187 2021-10-29 19:44:59 2001 19:44:33 10/29/21 26s UTILITY EVENT: OUTAGE
186 2021-10-29 19:44:31 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
185 2021-10-29 19:41:35 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
184 2021-10-29 19:41:26 2001 19:40:12 10/29/21 74s UTILITY EVENT: OUTAGE
183 2021-10-29 19:40:11 202E CLOCK DEFAULTED 19:40:11 10/29/21
182 2021-10-29 19:40:11 202B ALARM CLEARED :XM3-1 APP CLOCK NOT SET=0
181 2021-10-29 19:40:01 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
180 2021-10-29 19:39:59 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
179 2021-10-29 19:34:21 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
178 2021-10-29 19:34:21 202A MINOR ALARM :XM3-1 BATT TEMP PROBE =ALARM
177 2021-10-29 19:34:06 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
176 2021-10-29 19:34:06 202A MINOR ALARM :XM3-1 BATT TEMP PROBE =ALARM
175 2021-10-29 19:31:51 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
174 2021-10-29 19:31:51 202A MINOR ALARM :XM3-1 BATT TEMP PROBE =ALARM
173 2021-10-29 19:32:15 2029 MAJOR ALARM :XM3-1 Low Batt Disconnect=FAST
172 2021-10-29 19:32:03 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
171 2021-10-28 21:42:17 2038 ALARM CLEARED :XM3-1 ACTIVE DROP =0 NEW: 381W, OLD: 355W
170 2021-10-28 16:04:25 202B ALARM CLEARED :XM3-1 Low Batt Disconnect=OK
169 2021-10-28 15:59:00 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
168 2021-10-28 15:58:56 201A ALARM CLEARED :XM3-1 OUTPUT FAIL ALARM=OK
167 2021-10-28 15:42:22 201A MAJOR ALARM :XM3-1 OUTPUT FAIL ALARM=ALARM
166 2021-10-28 15:42:17 2038 WARNING :XM3-1 ACTIVE DROP =1 NEW: 0W, OLD: 357W
165 2021-10-28 15:42:15 2001 14:05:22 10/28/21 96m UTILITY EVENT: OUTAGE
164 2021-10-28 15:42:13 202B ALARM CLEARED :XM3-1 LOW BATTERY WARNING=OK
163 2021-10-28 15:42:13 2029 MAJOR ALARM :XM3-1 Low Batt Disconnect=STRING
162 2021-10-28 15:27:05 2029 MAJOR ALARM :XM3-1 LOW BATTERY WARNING=ALARM
<<Prev 1 2 3 4 5 6 7 8 Next>>

 