XM3.1-905-HPL
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM3.1-905-HPL
Firmware V0.03.4A
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Rest
Tamper Closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 120.88 V
Current 0.76 A
Power 75 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 7.00 A
Input Power Consumption 4,148 Wh
Output
Voltage 60.41 V
Power 25 W
Apparent Power 42.28 VA
Frequency 60.05 Hz
Percent Load 14.00 %
Output Setting 60 V
Output Regulation Coarse override
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 0.70 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.70 V/cell
Reduced Peak Mode Enable
Total Standby Events 257
Time Since Last Standby Event 17d 22h:02m
Time in Last Standby Event 0d 0h:01m
Total Time in Standby 5,533 min
Standby Events Since Reset 188
Time in Standby Since Reset 4,071 min
Time Since Reset 1,375 day(s)
Total Run Time 1,375 day(s)
Total Downtime 22d 14h:07m
Oil Cap Lifespan Consumed 29.9 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 23 day(s)
Test Duration 30 min
Test Interval 29 day(s)
Test Inhibit No

 